Input channels - electrical
| 4, each 4-20 mA loop powered by VDS104
|
Input channels - type
| Programmable as vibration, temperature or general
|
Sensor supply voltage
| 24 VDC nominal, current limited, fuse protected
|
Maximum wire run to sensor
| 2000 ft (+12 VDC at sensor, 20 mA loop current)
|
Absolute accuracy, inputs
| 3%
|
Resolution, vibration inputs
| 0.1% of full scale
|
Resolution, current inputs
| 0.01 mA
|
Alarm Thresholds
| 4, one for each vibration input
|
Warning Thresholds
| 4, one for each vibration input
|
Delay timers
| 8, one for each threshold
|
Delay Timer accuracy
| 1%
|
Delay timer range
| 0 to 99 seconds in 1 second increments
|
Output relays
| 8 SPDT fully programmable
|
Relay contact rating
| 10A, 125 VAC non-inductive load
|
Analog outputs
| 4, one for each input channel, 0-5 VDC
|
Analog output accuracy
| 5%
|
Operating Temperature Range
| +10 to +50 Celsius
|
AC power requirements
| 90-130 VAC, 12 W max, 60 Hz
|
Size
| 7.9”H by 11.8”L by 6.0”D not including latches
|
Weight
| Approx 6 lbs |